Specifications
Test Item of Cold Shrink Straight through Joint & Termination as per IEC-60502-4 / IS:13573
| Testing Items U o/U |
6.35/11 kV |
| A.C. withstand test |
29kV, 5min, no flashover |
| Partial discharge test |
11kV 10pc (Max.) |
| Thermal Cycles (63 cycles) |
under 95-100 ° C 16kV |
| Impulse voltage test |
75kV no flashover |
| A.C. with stand test |
16kV, 15 min, no flashover |
| Humidity test (Indoor) |
No flashover, tracking erosion ormechanical damage occured at 300hrs, 8kV |
| Salt Fog test (Outdoor) |
No flashover, tracking erosion ormechanical damage occured at 1000hrs, 8kV no flashover, tracking |
Order Reference:
For 11 kV Indoor Termination (for XLPE Cable)
For 11 kV Indoor Termination (for XLPE Cable)
Order Reference:
For 11 kV Outdoor Termination (for XLPE Cable)
For 11 kV Outdoor Termination (for XLPE Cable)