Specifications:
Dimension Chart for Heat Shrink Stress Control Tubing
Code |
As Supplied |
After Recovered |
ø D1 (max.) |
ø D2 (max.) |
T (min.) |
DSCT - 30/15 |
30 |
15 |
2.5 |
DSCT - 45/20 |
45 |
20 |
2.8 |
DSCT - 50/25 |
50 |
25 |
3.0 |
DSCT - 58/25 |
58 |
25 |
3.0 |
DSCT - 65/30 |
65 |
30 |
3.0 |
Note: All dimensions are in mm
Technical Data for Heat Shrink Stress Control Tubing
Property |
Requirements |
Test Method |
Physical |
Tensile Strength |
10 N/mm2 (min.) |
ASTM D 412 / ISO 37 |
Ultimate elongation |
200% (min.) |
ASTM D 412 / ISO 37 |
Water absorption (25oC) |
0.5% (max.) |
ASTM D 570 |
Thermal Ageing |
Continuous operating temperature |
-55oC to +130oC |
IEC 216 |
Shrink temperature |
120oC (min.) |
IEC 216 |
Heat shock (30 min. 200oC) |
No cracking / No flowing |
|
Heat ageing (168 hrs 120oC) |
Tensile strength |
8.0 N/mm2 (min.) |
ASTM D 412 / ISO 37 |
Ultimate elongation |
100% (min.) |
|
Low temperature flexibility (-20oC) |
No cracking |
ASTM D 2671 |
Electrical |
Volume resistivity |
1 x 109 Ω cm (min.) |
ASTM D 257 / IEC 93 |
Dielectric constant |
15 min. |