Heat Shrinkable Anti Tracking Rain Sheds
Features
- Designed for medium voltage applications up to 36 KV
- Shaped components to meet a variety of configuration requriements
- Continuous operation temperature: -55° C to 120° C
- High creep resistance, anti-tracking properties
Technical Data
Property
| Requirements |
Test Method |
Tensile Strength |
8N/mm2 (min.) |
ASTM D412, ESI 09-13 |
Elongation |
200% (min) |
ASTM D412, ESI 09-13 |
Heat Aging
(500 hrs. at 1200 C) |
|
|
Tensile Strength |
7N/mm2 (min.) |
ASTM D412 |
Elongation |
200% (min.) |
ASTM D412 |
Cold Temperature
Flex (-400 C) |
No cracking |
ASTM D2671 |
Electrical |
|
|
Dielectric Strength |
10 kV/mm (min.) |
ASTM D149, IEC 243 |
Volume Resistivity |
1 x 1012 ohm-cm (min.) |
ASTM D257 |
Track Resistance |
Non-Tracking |
ASTM D2303 |
Chemical Resistance |
|
|
Tensile Strength |
7N/mm2 (min.) |
ASTM D412 |
Elongation |
200% (min.) |
ASTM D412 |
Dimension Chart