Terminations

Heat Shrink Terminations up to 36 kV for PILC Cables

DENSONS HEAT SHRINKABLE TERMINATIONS UP TO 36 kV For 3 Core XLPE/EPR Insulated Cable

In conformance with IEEE-48, VDE 0278 & IS: 13573.

Heat Shrink Terminations upto 36 kV for PILC Cables

Specifications

TEST TEST TYPE PSO / E 24-36
A.C. Voltage withstand Dry : A. C. 75 kV / 1 min. Wet : 75 kV / 1 min.
D.C. Voltage withstand 144 kV for 30 min.
Impulse Voltage withstand 170 kV 10+VE & 10-VE Shots

In conformance with BS 6480, IEC 55 (Part I & II), VDE 0255, IS 692
Type Test Reports Available On Request

Ordering Information

CABLE SIZE (Sq. mm) FOR 24 kV INDOOR (Kit Code)  
3 x 25 - 50 PSE - 21 Enquire Now
3 x 70 - 120 PSE - 22 Enquire Now
33 x 150 - 240 PSE - 23 Enquire Now
3 x 300 - 400 PSE - 24 Enquire Now
CABLE SIZE (Sq. mm) FOR 24 kV OUTDOOR (Kit Code)  
3 x 25 - 50 PSO - 21 Enquire Now
3 x 70 - 120 PSO - 22 Enquire Now
33 x 150 - 240 PSO - 23 Enquire Now
3 x 300 - 400 PSO - 24 Enquire Now
CABLE SIZE (Sq. mm) FOR 36 kV INDOOR (Kit Code)  
3 x 35 - 70 PSE - 31 Enquire Now
3 x 95 - 150 PSE - 32 Enquire Now
3 x 185 - 300 PSE - 33 Enquire Now
3 x 400 - 500 PSE - 34 Enquire Now
CABLE SIZE (Sq. mm) FOR 36 kV OUTDOOR (Kit Code)  
3 x 35 - 70 PSO - 31 Enquire Now
3 x 95 - 150 PSO - 32 Enquire Now
3 x 185 - 300 PSO - 33 Enquire Now
3 x 400 - 500 PSO - 34 Enquire Now